3 Phase RAPS Inverter Specifications

PSA Inverter

 

 

 

Model
RAP-15-48
Discontinued
RAP-15-108
RAP-15-120
Discontinued
RAP-20-108
RAP-20-120
 
RAP-25-108
RAP-25-120
Discontinued
RAP-30-108
RAP-30-120
 
RAP-40-120
Input voltages 48 VDC 108/120 VDC 108/120 VDC 108/120 VDC 108/120 VDC 120 VDC
Operating DC voltage range 42-62 V 100-158 V 100-158 V 100-158 V 100-158 V 100-158 V
Continuous output @ 40°C 15 kW 15 kW 20 kW 25 kW 30 kW 40 kW
1 hour rating @ 40°C 18 kW 18 kW 24 kW 30 kW 36 kW 48 kW
½ hour rating @ 40°C 19.5 kW 19.5 kW 26 kW 32.5 kW 39 kW 52 kW
Surge rating 30 kW 30 kW 40 kW 50 kW 60 kW 80 kW
Maximum charge current 250 A 120 A 150 A 200 A 250 A 300 A
Peak efficiency > 91 % > 93 % > 93 % > 93 % > 93 % > 93 %
Power factor range 0 - 1 0 - 1 0 - 1 0 - 1 0 - 1 0 - 1
Idle power < 150 W < 150 W < 200 W < 250 W < 300W < 400W
Integrated isolation AC/DC cct breaker cct breaker cct breaker cct breaker cct breaker cct breaker
Indicators LED & LCD LED & LCD LED & LCD LED & LCD LED & LCD LED & LCD
Inverter mass 210 kg 290 kg 310 kg 330 kg 350 kg 390 kg
Internal Gen contactor no < 30 kVA < 30 kVA no no no
External Gen contactor required optional optional required required required

Common to all units:

  • Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
  • Low distortion, high power load presented to generator during charging for best generator performance.
  • All units available in 220 / 230 / 240 VAC 50 or 60 Hz output (240 / 415, 230 / 380V three phase plus neutral connection). 120 / 208 VAC on application.
  • Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
  • Cooling: Convection and thermostatically controlled fans.
  • Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
  • Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.

Standards:

All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
Low distortion, high power presented to to generator during charging for best generator performance.
Refer to sales staff for details of applicable compliance testing.

Brochures

Brochures for all PSA inverters canbe found here.

Application Notes

Application notes for Remote Area Power Systems inverters are available in PDF format. To view these documents, you will need Adobe's Acrobat Reader.

RAP Operation.pdf

This is a general description of RAPS inverter operation.

PSA Inverter Programming Example.pdf

This is a worked example, showing how to set up the parameters of a RAPS inverter for a solar-diesel remote power system. It was prepared by the Renewable Energy Centre at the Brisbane North Institute of TAFE, as part of their Hybrid Energy Systems course.