RAPS Inverter Specifications

Note that all these products are discontinued.
This detail is provided for information only.

Image of 3-5 kW RAPS inverter

Model

RAP-3-24-1

RAP-3-48-1

RAP-5-48

RAP-5-110

RAP-5-120

Input voltages

24 VDC

48 VDC

48 VDC

110 VDC

120 VDC

Output voltage & frequency*

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

Continuous output @ 40°C

2.7 kW

3 kW

5 kW

5 kW

5 kW

1 hour rating @ 40°C

3.2 kW

3.6 kW

6 kW

6 kW

6 kW

½ hour rating @ 40°C

3.5 kW

3.9 kW

6.5 kW

6.5 kW

6.5 kW

Surge rating

5.4 kW

6 kW

10 kW

10 kW

10 kW

Maximum charge current

90 A

35 A

83 A

35 A

35 A

Peak efficiency

> 90 %

> 92 %

> 92 %

> 94 %

> 94 %

Power factor range

0 - 1

0 - 1

0 - 1

0 - 1

0 - 1

Idle power

35 W

35 W

50 W

50 W

50 W

Standby power

< 10 W

< 10 W

< 10 W

< 10 W

< 10 W

Integrated isolation AC/DC

cct breaker

cct breaker

cct breaker

cct breaker

cct breaker

Indicators

LED & LCD

LED & LCD

LED & LCD

LED & LCD

LED & LCD

Inverter mass

60 kg

60 kg

70 kg

70 kg

70 kg

Data logging

Yes

Yes

Yes

Yes

Yes

Internal Gen contactor

6 kVA

6 kVA

10 kVA

10 kVA

10 kVA

External Gen contactor

optional

optional

optional

optional

optional

Remote access

RS232

RS232

RS232

RS232

RS232

 

Common to all units:

  • Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
  • Low distortion, high power load presented to generator during charging for best generator performance.
  • All units available in 220 / 230 / 240 VAC 50 or 60 Hz output (240 / 415, 230 / 380V three phase plus neutral connection). 120 / 208 VAC on application.
  • Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
  • Cooling: Convection and thermostatically controlled fans.
  • Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
  • Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.

Standards:

All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
Low distortion, high power presented to to generator during charging for best generator performance.
Refer to sales staff for details of applicable compliance testing.

Brochures

Brochures for all PSA inverters canbe found here.

Application Notes

Application notes for Remote Area Power Systems inverters are available in PDF format. To view these documents, you will need Adobe's Acrobat Reader.

RAP Operation.pdf

This is a general description of RAPS inverter operation.

PSA Inverter Programming Example.pdf

This is a worked example, showing how to set up the parameters of a RAPS inverter for a solar-diesel remote power system. It was prepared by the Renewable Energy Centre at the Brisbane North Institute of TAFE, as part of their Hybrid Energy Systems course.

 

*AC output voltages of 110, 120, 220 and 230 are available on application.
* DC operating voltage range 92% to 130% of nominal.